Green Tech Tools
  Shopping Cart Shopping Cart - 0 item(s)
 Speciality Tools
 AEMC
 Alnor Balometers
 Bacharach
 Cool Machines Fiber Blowers
 David White Instruments
 Fluke Test Equipment
 Green Tech Insulation Blowers
 Miller Fall Protection
 Retrotec Blower Door Systems
 Testo Test and Measurement
 Tramex Mositure Meters
 TSI Flow Hoods
 UEI Instruments
 

Home > Retrotec Blower Door Systems
Retrotec Q5E Air Blower Door
Part Number 1638
Retrotec Q5E Air Blower Door
Email this page to a friend Email this page to a friend
Review this item Review this item
Price
Your Price:   Contact for Price
Quantity
Description

Retrotec Q5E High Power Digital Modular Panel Air Blower Door Fan System with Modular Panels & Automatic Control - includes fan, guage, and door

The Q5E is a commercial quality automated blower-door at an economy price. Use for super tight to super leaky houses, small commercial buildings or enclosures with 13.5 ft2 (1.2m2) of leakage or less.

DM-2A Automatic Dual Channel Micro-manometer

  • Controls pressure or flow
  • results without a computer!
    • flow at any pressure, CFM50
    • air-changes / hour
    • leakage area, ELA
    • air-flow / area

3300 Automatic Calibrated High Power variable frequency drive Fan

  • 8000 cfm, even at 50 Hz
  • runs on both 110 and 240 Volts
  • computer controller built in
  • 7 flow ranges for leakage measurement of super tight to super leaky buildings

Fan Flow (accuracy +/- 5%, +/- 3% with Auto-Correct in Retrotec software) CFM Liters/~s~ m3/h
Maximum Flow in Free Air 8,100 3,823 13,762
Maximum Flow at 50 Pascal test pressure 8,000 3,776 13,592
At 50 Hz, NO power is lost due to variable frequency drive 8,000 3,776 13,592
Maximum Flow at 300 Pascal test pressure 4,000 1,888 6,796
Minimum Flow on Range Configuration C1 at 10 Pa 38 18 65
Dimensions inches cm
Fan height 26 66
Fan Depth 9.5 24.1
Fan Inlet Diameter 22 56
Panel height 76.5 to 87 194 to 221
Panel Case (included) 31 × 30 x 7 77 × 76 × 18
Panel Width 32 to 48.75 81 to 124
Fan weight 37lb. 16.8 kg.
Fan Motor 2.0 hp, 22 amps at 120 V
14 amps at 240 Volts
Panel weight 21.5 lb. 9.8kg.

Calibration meets: Canadian CGSB-149.1-2002 & SuperE, USA ASTM E 779 – 03, European EN 13829 & CEN, UK TM-23 Energy Standards, Rain Penetration Standards. NFPA 2001- 01, ISO 14520 and UBC-905 fire standards.

Specifications subject to change without notice. Infiltrometer is a registered trademark of Retrotec.

Optional Software Custom designed software is available from Retrotec for energy analysis, large building testing & fire enclosure integrity testing.

See literature on gauges, fans and panels for case options and accessories.

Product Information
Q5E Specifications Q5E Specifications
  Blower Door Testing Blower Door Testing
  Building Pressurization Building Pressurization
  Blower Doors and Duct Blasters Blower Doors and Duct Blasters
  Using Blower Door Data Using Blower Door Data


Related Items
Nikro 860757-22050 860757 22050 5HP 220V/50Hz 175 PSI Portable Electric Compressor
Nikro 860757-22050 860757 22050 5HP 220V/50Hz 175 PSI Portable Electric Compressor
Average Rating 0 Review(s)
Your Price: Contact for Price (877) 801-5693
Nikro UA2005 UA 2005 115V 60Hz Upright Portable Air Scrubber
Nikro UA2005 UA 2005 115V 60Hz Upright Portable Air Scrubber
Average Rating 0 Review(s)
Your Price: $950.00
Nikro 860322 9HP Honda 2 Stage 175 PSI Portable Gasoline Compressor
Nikro 860322 9HP Honda 2 Stage 175 PSI Portable Gasoline Compressor
Average Rating 0 Review(s)
Your Price: Contact for Price (877) 801-5693

Green Tech Tools Affiliate Program