Kimo VT 200 H Specifications |
|
Measuring Units |
Measuring Ranges |
Accuracy* |
Resolutions |
CURRENT / VOLTAGE |
|
V, mA |
0 - 2.5 V 0 - 10 V 0 - 4/20 mA |
+/-2mV +/-10mV +/-0.01mA |
0.001 V 0.01 V 0.01 mA |
THERMOCOUPLE (See related datasheet) |
|
deg. C, deg. F |
K : -200 - 1300 deg. C J : -100 - 750 deg. C T : -200 - 400 deg. C |
+/-1.1 deg. C or +/-0.4percent rdg.** +/-0.8 deg. C or +/-0.4percent rdg.** +/-0.5 deg. C or +/-0.4percent rdg.** |
0.1 deg. C 0.1 deg. C
0.1 deg. C |
HOTWIRE - Standard & telescopic |
Air velocity
temp. Airflow |
m/s, fpm, Km/h
deg. C, deg. F m3 /h, cfm, l/s, m3 /s |
0.15 - 3 m/s 3.1 - 30 m/s
-20 - +80 deg. C 0 - 99,999 m3/h |
+/-3percent rdg. +/-0.03 m/s +/-3percent rdg. +/-0.1 m/s
+/-0.3percent rdg. +/-0.25 deg. C +/-3percent rdg. +/-0.03*area(cm2 ) |
0.01 m/s 0.1 m/s
0.1 deg. C 1 m3/h |
Ø 100 mm VANE PROBE |
Air velocity
temp. Airflow |
m/s, fpm, Km/h
deg. C, deg. F m3 /h, cfm, l/s, m3 /s |
0.3 - 3 m/s 3.1 - 35 m/s
-20 - +80 deg. C 0 - 99,999 m3/h |
+/-3percent rdg. +/-0.1m/s +/-1percent rdg. +/-0.3m/s
+/-0.4percent rdg. +/-0.3 deg. C +/-3percent rdg. +/-0.03*area(cm2 ) |
0.01 m/s 0,1 m/s
0.1 deg. C 1 m3/h |
Ø 70 mm VANE PROBE |
Air velocity
temp. Airflow |
m/s, fpm, Km/h
deg. C, deg. F m3 /h, cfm, l/s, m3 /s |
0.3 - 3 m/s 3.1 - 35 m/s
-20 - +80 deg. C 0 - 99,999 m3/h |
+/-3percent rdg. +/-0.1m/s +/-1percent rdg. +/-0.3m/s
+/-0.4percent rdg. +/-0.3 deg. C +/-3percent rdg. +/-0.03*area(cm2 ) |
0,1 m/s
0.1 deg. C 1 m3/h |
Ø 14 mm VANE PROBE |
Air velocity
temp. Airflow |
m/s, fpm, Km/h
deg. C, deg. F m3 /h, cfm, l/s, m3 /s |
0.8 - 3 m/s 3.1 - 25 m/s
-20 - +80 deg. C 0 - 99,999 m3/h |
+/-3percent rdg. +/-0.1m/s +/-1percent rdg. +/-0.3m/s
+/-0.4percent rdg. +/-0.3 deg. C +/-3percent rdg. +/-0.03*area(cm2 ) |
0,1 m/s
0.1 deg. C 1 m3/h |
WIRE OR WIRELESS Pt100 (See related datasheet) |
|
deg. C, deg. F |
-50 - +250 deg. C-(According - model) |
+/-0.3percent rdg. +/-0.25 deg. C-(According - model) |
0.01 deg. C |